AVT, AVTV, AVTVU
Insulated wires for overhead lines. Wires AVT, AVTV and AVTVU with steel cable messenger. TU16.K71-015-87. These wires are designed for transmission and distribution of electrical energy in power and lighting networks with AC voltage up to 380 kV at 50 Hz.
AVT is a wire made of solid aluminium conductors in PVC insulation with a cable messenger made of 7 galvanized steel wires. It is designed to be laid outdoors for in-feeding to residential and other buildings in I and II icing degree regions. AVTV is a lightweight wire made of solid aluminium conductors in PVC insulation with a cable messenger made of 7 galvanized steel wires. It is designed for indoor use. AVTVU is a wire made of solid aluminium conductors in PVC insulation with a reinforced cable messenger made of 19 galvanized steel wires. It is designed for indoor use when higher mechanical strength is required.| Number of conductors and their nominal cross-section, mm2 | Nominal diameter, mm | Estimated weight of 1 km of the wire, kg |
|---|
| AVT | AVTV, AVTVU | AVT | AVTV | AVTVU |
|---|
| 2x2.5 | 7,4 | 7,0 | 47,1 | 44,2 | 69,5 |
| 3x2.5 | 8,4 | 7,9 | 62,7 | 58,6 | 79,5 |
| 4x2.5 | 9,5 | 8,7 | 78,6 | 73,0 | 93,0 |
| 2x4.0 | 9,3 | 8,4 | 65,4 | 58,5 | 79,4 |
| 3x4.0 | 10,5 | 9,4 | 90,4 | 80,0 | 101 |
| 4x4.0 | 11,9 | 10,5 | 115 | 102 | 123 |
| 4x6.0 | 13,2 | 11,9 | 146 | 131 | 152 |
| 4x10 | 16,5 | 15,0 | 226 | 206 | 227 |
| 4x16 | 20,6 | 19,2 | 348 | 306 | 379 |
Designed for operation at an ambient temperature between -50 and +50°C and relative air humidity up to 98% at a temperature up to 40°C.
Factory length – at least 110 m.
Service life is 7 years.